General Data for Battery
Storage-30-20 | Storage-50-20 | |
---|---|---|
Width x height x depth of battery cabinet (without hand bracket) | 608 mm x 1408 mm x 808 mm | 608 mm x 2008 mm x 808 mm |
Width x height x depth of battery cabinet (with hand bracket) | 608 mm x 1408 mm x 990 mm | 608 mm x 2008 mm x 990 mm |
Tilt dimension of battery cabinet to front and rear | 1607 mm | 2155 mm |
Tilt dimension of battery cabinet to side | 1519 mm | 2090 mm |
Weight of battery cabinet with battery management system and with maximum number of battery modules | 356 kg | 555 kg |
Weight of battery cabinet without battery management system and without battery modules | 119 kg | 150 kg |
Weight of battery module | 56 kg | 56 kg |
Weight of battery management system (APU) | 13 kg | 13 kg |
Maximum installation height above MSL | 2000 m | 2000 m |
Degree of protection (according to IEC 60529) | IP20 | IP20 |
Protection class (according to IEC 62109-1) | I | I |
Pollution Degree | PD 2 | PD 2 |
Maximum noise emission per running fan in battery cabinet | 65 dB | 65 dB |
System warranty | 10 years | 10 years |
Capacity warranty | 10 years | 10 years |
Recycling | Free collection of batteries within Germany | Free collection of batteries within Germany |
Certificates and standards for battery cell | IEC 62619, UL 1642, UN 38.3 | IEC 62619, UL 1642, UN 38.3 |
Certificates and standards for battery module | UN 38.3, UL 1973, IEC 62619:2017, IEC 62620:2014 | UN 38.3, UL 1973, IEC 62619:2017, IEC 62620:2014 |
Certificates and standards for battery | CE, UN 38.3, IEC 62619:2017, IEC 61010-1+A1:2016, IEC 61508:2010, IEC 61000-6-2:2016, IEC 61000-6-4:2019, IEC 61000-6-7:2015, 2006/66/EC (Battery Directive) | CE, UN 38.3, IEC 62619:2017, IEC 61010-1+A1:2016, IEC 61508:2010, IEC 61000-6-2:2016, IEC 61000-6-4:2019, IEC 61000-6-7:2015, 2006/66/EC (Battery Directive) |
Battery designation in accordance with DIN EN 62620:2015 | INP46/175/127/[1P22S]M/-20+60/90 | INP46/175/127/[1P22S]M/-20+60/90 |