Event 3401


Qualified person

Event message:

  • DC overvoltage

  • Disconnecting the DC side

Explanation:

Overvoltage at the DC input. This can destroy the inverter.

Corrective measures:

  • Immediately disconnect the inverter from all voltage sources.

  • Check whether the DC voltage is below the maximum input voltage of the inverter. If the DC voltage is below the maximum input voltage of the inverter, reconnect the DC cables to the inverter.

  • If the DC voltage is above the maximum DC voltage of the inverter, ensure that the correct battery has been selected.

  • If this message is repeated frequently, contact the Service.