Disconnecting the Connections on the Battery
Qualified person
- Disconnect the battery from voltage sources ( > Disconnecting the Battery from Voltage Sources).
- On the battery management system of each battery cabinet, detach the connection cable of the external switch from the EXT SWITCH socket.
- On the battery management system of each battery cabinet, disconnect the connectors of the communication cables.
- On the battery management system of each battery cabinet, disconnect the connectors of the DC cables.
- On the battery modules of each battery cabinet, disconnect the connectors of the communication cables.
- On the battery modules of each battery cabinet, disconnect the connectors of the DC cables.
- On the central ground point of each battery cabinet, undo the bolted ground conductor connection (hexagon socket, AF13).
- Remove all cables from the battery cabinet.
- Detach the grounding cable of the battery management system from the grounding point. To do this, loosen the M6 terminal lug (hexagon socket, AF10).