Installation Plans


Do not place a battery cabinet under an inverter

If a battery cabinet is placed under an inverter, the waste heat produced by the battery inverter may be blown behind the battery cabinet. It is therefore not permitted to place a battery cabinet under an inverter.

12499345292

Example for installation of a system with one battery cabinet

The standard system configuration uses cable lengths of 5 m.

Position

A

Battery cabinet

B

Battery inverter

11971549068

Example for installation of a system with four battery cabinets

Position

A

Battery cabinet

B

DC distributor

C

Battery inverter

In a system configuration with a number of battery cabinets, it is recommended to install the DC distributor centrally between the battery cabinets so that the DC cables to each battery cabinet can be kept as short as possible and the same length. Take the length of the supplied DC cables into account.

Up to four battery cabinets can be placed directly next to each other without any clearance required between them. If more than four battery cabinets are to be placed beside each other, a minimum clearance of 600 mm to the next battery cabinet must be observed after four battery cabinets.