Requirements for the Temperature and Humidity Sensor Installation Site


WARNING

Danger to life due to fire or explosion

Despite careful construction, electrical devices can cause fires. This can result in death or serious injury.

  1. Do not mount the product in areas containing highly flammable materials or gases.
  2. Do not mount the product in potentially explosive atmospheres.
  • A temperature and humidity sensor must be installed wherever a battery cabinet is installed.

  • Clearance between temperature and humidity sensor and battery cabinet: 1 m to 5 m

  • Clearance between temperature and humidity sensor and mains connection (AC 230 V): < 1200 mm

  • There must be no electrical devices at the temperature and humidity sensor installation site.

  • There must be no heat and cold sources at the temperature and humidity sensor installation site.