Uninstalling the Battery Management System (APU)
- Disconnect the inverter and battery from voltage sources.
Procedure:
- Remove the external switch line between the Battery Management System (APU) and the battery cabinet (external switch).
- Remove the DC lines from the Battery Management System to the first and last battery module and to the inverter.
- Remove the communication cables from the Battery Management System to the first battery module and to the inverter if necessary.
- Loosen and remove the M6x16 pan-head screws (crosshead) with plastic washers from the pre-installed cage nuts.
- Pull the Battery Management System slightly out of the battery cabinet so that you can reach the grounding cable at the rear of the Battery Management System.
- Use a torque wrench (10 mm) to undo the grounding cable and ground connection and remove the Battery Management System from the battery cabinet.