Earthing the battery cabinet
Qualified person
DANGER
Danger to life due to electric shock due to touching live components or cables with insufficient or no grounding
If there is insufficient or no earthing, high voltages can be present at the battery cabinet enclosure in the event of a fault. Touching live parts and cables results in death or lethal injuries due to electric shock.
- Earth the battery cabinet.
- Earth the battery management system during installation.
Procedure:
- Connect the supplied grounding cable to the battery cabinet grounding point (hexagon socket, AF13, torque: 8 Nm).