Set the digital input for a ripple control receiver or remote terminal unit
Requirements:
The SMA I/O Module is mounted and connected (see manual for the SMA I/O Module)
At least firmware version 3.02.xx.R must be installed on the inverter.
The user interface of the inverter is open and you are logged in.
Procedure:
- Select the menu item I/O configurations in the Configuration menu.
- Follow the steps of the commissioning wizard. For every setting made in a step, click on [Next].
- Enable the inputs B2, B3, B4, and A2 required for connecting the ripple control receiver or remote terminal unit on the SMA I/O Module.
- When all settings are made, the inverter starts the communication connection with the ripple control receiver or remote terminal unit.
- The user interface shows the current digital input configuration.