Switching the Inverter On


Qualified person

Requirements:

  • The AC circuit breaker must be correctly rated and mounted.

  • The inverter must be correctly mounted.

  • All cables must be correctly connected.

Procedure:

    10875399052
  1. Position the enclosure lid. The two guide pins on the enclosure lid must slide into the guide openings on the enclosure.
  2. 10875399436
  3. Ensure that the cover sits straight on the enclosure.
  4. 10875399820
  5. Hold the enclosure lid pressed against the enclosure and screw it tight. (Hex socket, AF 8, torque: 18 Nm).
  6. 10875400204
  7. Place the cover on the screw in the enclosure lid.
  8. Connect the battery via the external DC switch.
  9. Switch on the AC circuit breaker.
  10. If the green and red LEDs flash simultaneously during initial commissioning, operation is stopped because no country data set has been set yet. For the inverter to begin operation, the configuration must be completed and a country data set must be set.
  11. If the green LED is still flashing, the conditions for the discharge and charge mode are not yet met. As soon as the conditions for the discharge and charge mode are met, the inverter will start charging and discharging. Depending on the available power, the green LED is continuously illuminated or pulses.
  12. If the red LED lights up, an event has occurred. Find out which event has occurred and, if necessary, initiate countermeasures.