Connecting the AC Cable
Qualified person
Requirements:
The medium-voltage transformer used must be suitable for the product.
Additionally required material (not included in the scope of delivery):
Protective grease (only for conductors made of aluminum)
Procedure:
- Ensure that the AC miniature circuit breaker is switched off and that it cannot be reconnected.
- Shorten the cable if necessary.
- Dismantle the cable.
- Strip the insulation on the insulated conductors each by 30 mm.
- Remove any cable remnants from the product.
- For conductors made of aluminum, remove any oxide film and apply protective grease to the conductors.
- Connect PE, N, L1, L2 and L3 to the terminals according to the label. To do so, position each conductor as far as they will go into the corresponding terminal and tighten the screw of the terminal (hex socket AF 5, torque for a conductor cross-section of 16 mm² to 95 mm²: 20 Nm).
- Ensure that the correct conductors are assigned to the terminals.
- Ensure that all conductors are securely in place.


Also see: