Event message:
F972 Isolation Fault
Explanation:
DC cabling insulation fault: The differential current measured is too high.
Corrective measures:
Disconnect the battery and inverter from voltage sources.
Check the grounding connection on the battery cabinet.
Check the grounding connection on the battery management system.
Check the DC cabling.
Contact the Service.