Event F972


Qualified person

Event message:

  • F972 Isolation Fault

Explanation:

DC cabling insulation fault: The differential current measured is too high.

Corrective measures:

  • Disconnect the battery and inverter from voltage sources.

  • Check the grounding connection on the battery cabinet.

  • Check the grounding connection on the battery management system.

  • Check the DC cabling.

  • Contact the Service.