Defaults for Addresses and Terminators
This sections contains the defaults for addresses and terminators for a system with one inverter and two to four battery cabinets. For systems with more than one inverter, the same defaults apply for each inverter.
The defaults for address and terminator on each battery cabinet are based on the following system variants:
System with one primary battery cabinet and one secondary battery cabinet
System with one primary battery cabinet and two secondary battery cabinets
System with one primary battery cabinet and three secondary battery cabinets
System with one primary battery cabinet and one secondary battery cabinet
Device | Address | Terminator |
---|---|---|
Primary battery cabinet | ADDRESS setting: 0/0 Left rotary switch to 0 Right rotary switch to 0 | TERM switch to ON |
Secondary battery cabinet 1 | ADDRESS setting: 2/0 Left rotary switch to 2 Right rotary switch to 0 | TERM switch to ON |
System with one primary battery cabinet and two secondary battery cabinets
Device | Address | Terminator |
---|---|---|
Primary battery cabinet | ADDRESS setting: 0/0 Left rotary switch to 0 Right rotary switch to 0 | TERM switch to ON |
Secondary battery cabinet 1 | ADDRESS setting: 2/0 Left rotary switch to 2 Right rotary switch to 0 | TERM switch to OFF |
Secondary battery cabinet 2 | ADDRESS setting: 2/1 Left rotary switch to 2 Right rotary switch to 1 | TERM switch to ON |
System with one primary battery cabinet and three secondary battery cabinets
Device | Address | Terminator |
---|---|---|
Primary battery cabinet | ADDRESS setting: 0/0 Left rotary switch to 0 Right rotary switch to 0 | TERM switch to ON |
Secondary battery cabinet 1 | ADDRESS setting: 2/0 Left rotary switch to 2 Right rotary switch to 0 | TERM switch to OFF |
Secondary battery cabinet 2 | ADDRESS setting: 2/1 Left rotary switch to 2 Right rotary switch to 1 | TERM switch to OFF |
Secondary battery cabinet 3 | ADDRESS setting: 2/2 Left rotary switch to 2 Right rotary switch to 2 | TERM switch to ON |