Heat Losses and Active Power Output
The heat losses and the active power output of the battery are dependent on the C rate, the charging and discharging current of the battery, and the number of modules. All indicated values refer to the end of the battery life and can be lower at the beginning of use.
C rate per battery module | 1 C | 0.75 C | 0.50 C | 0.25 C | 0.1 C |
---|---|---|---|---|---|
Charging and discharging current per battery module | 100 A | 75 A | 50 A | 25 A | 10 A |
Heat loss per battery module at the end of the battery life | 251 W | 141 W | 63 W | 16 W | 2.5 W |
Active power output with ten battery modules per battery cabinet | 2509 W | 1412 W | 628 W | 157 W | 25 W |
Active power output with eight battery modules per battery cabinet | 2008 W | 1130 W | 502 W | 126 W | 20 W |
Active power output with six battery modules per battery cabinet | 1506 W | 847 W | 377 W | 94 W | 15 W |
Active power output with four battery modules per battery cabinet | 1004 W | 565 W | 251 W | 63 W | 10 W |