Information on the Battery Module


The battery must be commissioned no longer than six months after manufacture or cyclization. If the battery cannot be commissioned within six months of manufacture or cyclization, recyclization of the battery storage system is required. This section describes the information on the battery module that is required for cyclization.

Information

Explanation

Serial Number

The Serial Number summarizes the following information:

  • Material number: STOR-MOD-8k-20

  • The date of manufacture is a 4-digit numerical code that indicates the week and year of manufacture. Example: The specification +1124+ gives the date of manufacture as the 11th week of 2024.

  • The serial number of the battery module is structured as follows: SA xxxxxx

The Serial Number of the battery module can be found on the packaging box and on the front of the battery module on the right side of the fan.

Manufacturing Date

The manufacturing date of the battery module can be found on the battery module enclosure and packaging box.

Last cyclization Date

If the battery module has undergone recyclization, the last cyclization date can be found on the battery module enclosure.

Best Before Date

The latest possible date for commissioning the battery module can be found on the battery module enclosure and packaging box.

If the battery module has not been commissioned by this date, recyclization is required. Recyclization can be requested from Service.

Commissioning the battery module after the Best Before Date without performing a recyclization will invalidate any warranty claims (warranty conditions can be found at www.SMA-Solar.com).