Requirements for Output Voltage and State of Charge


Before extension of the battery can begin, the battery must meet the following requirements for DC output voltage and state of charge.

Storage-30-20

DC output voltage with four battery modules

313.4 V to 315.4 V

DC output voltage with five battery modules

392 V to 394 V

DC output voltage with six battery modules

470.6 V to 472.6 V

State of charge

20 %

Storage-50-20

DC output voltage with seven battery modules

549.2 V to 551.1 V

DC output voltage with eight battery modules

627.8 V to 629.8 V

DC output voltage with nine battery modules

706.4 V to 707.4 V

DC output voltage with ten battery modules

785 V to 787 V

State of charge

20 %