Requirements for Output Voltage and State of Charge
Before extension of the battery can begin, the battery must meet the following requirements for DC output voltage and state of charge.
Storage-30-20 | |
---|---|
DC output voltage with four battery modules | 313.4 V to 315.4 V |
DC output voltage with five battery modules | 392 V to 394 V |
DC output voltage with six battery modules | 470.6 V to 472.6 V |
State of charge | 20 % |
Storage-50-20 | |
---|---|
DC output voltage with seven battery modules | 549.2 V to 551.1 V |
DC output voltage with eight battery modules | 627.8 V to 629.8 V |
DC output voltage with nine battery modules | 706.4 V to 707.4 V |
DC output voltage with ten battery modules | 785 V to 787 V |
State of charge | 20 % |