Parameters for the "Multiuse" function
The "multi-use" function can be defined with the following settings:
Parameter | Description |
---|---|
Purchased energy limit | Definition of the maximum power that may be obtained from the utility grid. If this power is exceeded, the battery is discharged to reduce the peak load. |
SOC limiting value | Distributing the total capacity of the battery to use "peak shaving" or for increased self-consumption |
Hysteresis | Extension of the range for the switching limit defined by the SOC limiting value. This extension is applied symmetrically around the SOC limiting value. A hysteresis of 3% at a SOC limiting value 50% means a switching range of 47% to 53%. |
Feed-in limit | Definition of the power from which the battery is recharged. This value depends on the peak loads to be expected and must be defined on a project-by-project basis. |
Information: To use the peak load shaving function, a purchasing tariff including peak load prices is necessary.