Changing the Meter Configuration


In the Meter configuration area the data are displayed that were entered during commissioning and registration of the system Creating a Sunny Home Manager System in Sunny Portal)

  • A change is only possible under Extended configuration.

Only adjust the meter configuration for changes that are absolutely necessary

This might be the case, for example, if the grid operator demands a faster reaction for the dynamic active power limitation or for the zero feed-in (zero export). Contact your grid operator for information and observe the applicable standards and SMA manufacturer declarations.

Procedure:

  1. Select [Edit] on the tab for the device setting of the Sunny Home Manager.
  2. In the Meter configuration area in the fields Supply and feed-in as well as PV power generation, select the required feed-in and grid-supply meter as well as PV generation meter from the drop-down list.
  3. Select the required measuring interval from the Measuring interval internal energy meter drop-down list. Do not change the default 1000 ms unless this is required by standards (see corresponding manufacturer declarations and unit certificates).
    Information: If the internal energy meter is not used as the meter, the measuring interval must be set directly on the meter (e.g. an SMA Energy Meter) used.
  4. Enter the IP addresses of all devices (up to 3) that require this data (e.g. battery inverters, stand-alone inverters or hybrid inverters) in the input fields under Direct meter communication only if communication problems occur.
    Information: If an entry was made here, the meter telegram is no longer sent as a multicast telegram as before. This might cause problems with third-party devices.
  5. Click on [Save].