Requirements for connecting the voltage supply
Requirements:
The setpoints of the electric utility company must be observed.
The product can be operated single-phase or three-phase. Since the product is supplied with electric current by the screw terminal L1, at least the line conductor L1 and the neutral conductor N must be connected in order that the Sunny Home Manager switches on.
When using fine stranded conductors, bootlace ferrules must be used.
Cable requirements:
Conductor cross-section for measurements up to 63 A: 10 mm² to 25 mm²
Conductor cross-section with current transformer: at least 1.5 mm², for more information see recommendations of the current transformer manufacturer