Connecting Modbus Device Moxa E1214
The Modbus device Moxa E1214 can fulfill 2 functions:
Limit the feed-in power via ripple control receivers.
Control SG-ready devices such as heat pumps.
Procedure:
- Disconnect the connection point from voltage sources and make sure it cannot be reconnected.
- Connect devices to Moxa E1214. To do this, refer to the table below and to the device documentation.
- In the Sunny Home Manager, in the Modbus configuration, set up the Modbus profile.
Component | Use | Connection to Moxa E1214 | Modbus profile |
---|---|---|---|
Ripple control receiver Only 1 terminal may be active. | Limitation 0% | DI0 + GND | MOXA1214_PLimit |
Limitation 30% | DI1 + GND | MOXA1214_PLimit | |
Limitation 60% | DI2 + GND | MOXA1214_PLimit | |
Limitation 100% | DI3 + GND | MOXA1214_PLimit | |
SG-ready device | Open-loop control | R0_NO + R0_C | MOXA1214 or MOXA1214_PLimit |