Requirements for the RS485 interface


The product is suitable for the communication with RS485 devices via Modbus RTU.

The interface parameters must be set as follows:

Set-up:

8 data bits

1 stop bit

no parity

Cable requirements:

The cable length and quality affect the quality of the signal. Observe the following cable requirements.

  • Number of insulated conductor pairs and insulated conductor cross-section: at least 2 x 2 x 0.22 mm²

  • Maximum cable length across the entire RS485 bus: 1200 m

  • Twisted pair conductors

  • Cable with shielding: Yes

  • UV-resistant if installed outdoors.