Connect signal source to MFR
Qualified person
Requirements:
The technical requirements of the multifunction relay must be met ( > Technical Data).
Procedure:
- Disconnect the charging station from voltage sources ( > Disconnecting the product from voltage sources).
- Run the cable to the MFR slot.
- Strip 6 mm of the cable insulation at maximum.
- Unlock the conductor inserts on the provided 3-pole connector.
- Connect the cable to the 3-pole terminal block according to the operating mode. Ensure that the conductors are plugged completely into the terminal points up to their insulation.
- Insert the three-pole terminal block with the connected conductors into the MFR slot.
- Secure the cable to a strut using a cable tie, and cut off the protruding end of the cable tie with a suitable tool.
- Ensure that the terminal block is securely in place.
- Ensure that all conductors are correctly connected.
- Ensure that the conductors sit securely in the terminal points. Tip: To release the conductors, open the terminal points using a suitable tool.