Load-break switch and cable protection


NOTICE

Damage to the charging station due to the use of screw-type fuses as load-break switches

Screw-type fuses (e.g. DIAZED fuse or NEOZED fuse) are not load-break switches.

  1. Do not use screw-type fuses as load-break switches.
  2. Use a load-break switch or circuit breaker as a load disconnection unit (for information and design examples, see the Technical Information "Miniature circuit breaker" at www.SMA-Solar.com).
  • In systems with multiple charging stations, protect each charging station with a separate circuit breaker. Make sure to observe the maximum permissible fuse protection Technical Data). This will prevent residual voltage from being present at the corresponding cable after disconnection.

  • LoLoads installed between the charging station and the circuit breaker must be fused separately.

  • The overcurrent protective device for the AC output circuit is to be provided by others.