Connecting the AC Cable


Qualified person

Requirement:

  • The enclosure cover has been removed.

Procedure:

  1. Disconnect the circuit breaker for all line conductors and secure against reconnection.
  2. Dismantle the AC cable.
  3. Strip off the conductor insulation by 18 mm to 20 mm each.
  4. If necessary, provide each conductor with a bootlace ferrule.
  5. 13855920012
  6. Connect the grounding conductor according to the labeling.
  7. 13855920396
  8. Connect N according to the labeling.
  9. 14552441100
  10. Depending on the requirements, connect the conductor L1 according to the labeling.
  11. 13855920780
  12. Depending on the requirements, connect the conductors L1, L2, and L3 according to the labeling.
  13. Ensure that the correct conductors are assigned to all the terminals.
  14. Ensure that all conductors are securely in place.