Configuring the External Current Transformer
Qualified person
If the integrated measuring unit of the Sunny Home Manager is connected directly, it can measure a maximum current of 63 A per phase. Current transformers must be used to measure currents > 63 A per phase.
Procedure:
- Go to Device management via the side menu Configuration.
- Open the context menu of the Sunny Home Manager via the button .
- Select Display device properties.
- Start the edit via the button in the Advanced configurations area.
- Make the settings in the External current transformer area.
- Check the Use external current transformer? item.
- Enter the specified values of the current transformer (default setting: 1 each) in the fields Primary current: and Secondary current.
- Confirm with [Save].