Requirements for mounting
The mounting location must be indoors.
The Sunny Home Manager must be installed in a switch cabinet.
The short-circuit current (circuit distributor or subdistributor) must not exceed 6 kA.The installation site must be protected against dust, moisture, and hazardous substances.
The cable route from the mounting location to the router must not exceed a maximum length of 100 m.
A minimum distance of 1 m must be maintained from devices using the 2.4 GHz radio spectrum (e.g. WLAN devices, microwave ovens). This will prevent reduced connection quality and data transmission speed.
The ambient conditions at the mounting location must be suitable for the operation of the Sunny Home Manager ( > Technical Data).