Event 039 (Sunny Portal: 3501)
Qualified person
Event message:
Low system insulation resistance
Explanation:
Generally, the fault is caused by poor insulation of the module/cable to ground or by rainfall and a moist environment.
Corrective measures:
Check whether the ISO insulation conservation value is excessively high and ensure it complies with the local requirements.
Check the resistance of the DC string or DC cable to ground. Rectify the fault if a short circuit or a damaged insulating layer is present.
If the cable shows no abnormalities and the fault occurs on rainy days, check again when the weather is good.
If the fault cannot be rectified using the indicated corrective measures, contact Service.