Event 548-563 (Sunny Portal: 4002)
Qualified person
Event message:
String [#] disturbance of the output current
Corrective measures:
Check whether the PV module is shaded, heavily soiled or covered with snow.
Ensure that the PV module shows no signs of abnormal aging.
Ensure that the grid frequency is not increased. In this case, the inverter switches off individual strings due to derating.
Ensure that the string is not connected with reverse polarity.