Event 015 (Sunny Portal: 103)
 Qualified person
Qualified person
Event message:
- Grid overvoltage 
Explanation:
The grid voltage is higher than the set conservation value.
Corrective measures:
- Wait until the grid voltage is within the normal range again. 
- If the error occurs repeatedly, measure the present grid voltage and contact the local grid operator concerning solutions if the supply grid voltage is higher than the set value. 
- Ensure that the protection parameters are set correctly. 
- Ensure that the cross section of the alternating current cable meets the requirements. 
- If the fault cannot be rectified using the indicated corrective measures, contact Service.