Event 010 (Sunny Portal: 1302)


Qualified person

Event message:

  • Grid power failure

Explanation:

Alternating current switch or alternating current circuit is not connected.

Corrective measures:

  • Wait until the alternating current switch or alternating current circuit reconnects again. The inverter is reconnected to the supply grid automatically.

  • Check whether the supply from the utility grid is normal.

  • Ensure that the AC cable is correctly connected.

  • Ensure that the conductors of the AC cables are connected to the correct terminals.

  • Ensure that AC circuit breaker is connected and switched on.

  • If the fault cannot be rectified using the indicated corrective measures, contact Service.