AC Output
| Rated power at nominal AC voltage, 50 Hz | 110000 W | 
| Maximum apparent power at cos φ = 1 | 110000 VA | 
| Rated apparent power at cos φ = 1 | 110000 VA | 
| Nominal grid voltage | 400 V | 
| Rated grid voltage | 400 V | 
| Voltage range1) | 320 V to 460 V | 
| Rated current at nominal grid voltage | 158.8 A | 
| Maximum output current | 158.8 A | 
| Maximum residual output current | 420 A | 
| Duration of the maximum residual output current | 1 ms | 
| Total harmonic distortion | < 3 % | 
| Inrush current | < 10% of the nominal AC current for a maximum of 10 ms | 
| Rated grid frequency | 50 Hz | 
| Grid frequency1) | 50 Hz / 60 Hz | 
| Operating range at grid frequency 50 Hz | 45 Hz to 55 Hz | 
| Operating range at grid frequency 60 Hz | 55 Hz to 65 Hz | 
| Power factor at rated power | 1 | 
| Displacement power factor, adjustable | 0.8 overexcited to 0.8 underexcited | 
| Feed-in phases | 3 | 
| Connection phases | 3 grounding conductor | 
| Overvoltage category as per IEC 62109-1 | III | 
1) Depending on the configured country data set