Activating the Fast Stop Function
Qualified person
After the installation, the fast stop function must be activated via the user interface of the inverter. The following procedure must be carried out for each individual inverter.
Requirements:
The contact for the fast stop is connected to digital input ( > Connecting contact for fast stop to digital input).
You are logged in on the user interface as Service provider ( > Logging into the user interface as a service provider).
Procedure:
- In parameter group Extended Model 2-1 set the parameter DIEmShutd to On.
- If a fast stop is to be triggered when the contact is open: Set the parameter FsDIConfig in the parameter group Extended Model 2-1 to On.
- If a fast stop is to be triggered when the contact is closed: Set the parameter FsDIConfig in the parameter group Extended Model 2-1 to Off.