Resetting the arc-fault circuit interrupter (AFCI)
Qualified person
The basic procedure for changing operating parameters is explained in another section ( > Changing Operating Parameters).
After 5 detections per day the inverter must be reconnected manually via the user interface of the inverter.
Requirements:
Your inverter is equipped with AFCI. The type label of your inverter indicates whether your inverter has AFCI.
You are logged in on the user interface as Service provider ( > Logging into the user interface as a service provider).
Procedure:
In the parameter group Extended Model 2-1 RW select the parameter Clear AFCIAlarmEn and set it to On.
Also see: