Procedure for commissioning in systems with System Manager


Qualified person

This section describes the procedure of commissioning an inverter that is used in systems with System Manager (e.g. SMA Data Manager or an inverter that is configured as System Manager). In this case, the inverter is controlled or regulated by the System Manager.

It provides an overview of the steps, which must be performed in the prescribed sequence.

Procedure

See

Commission the inverter.

Commissioning the Product)

Commission the System Manager.

Manual of the System Manager

Register the inverter as an SMA Modbus device in the System Manager and make the initial configuration of the inverter via the System Manager. The configuration is transferred to the inverter and the settings of the inverter are overwritten.

Commissioning Assistant of the System Manager

Establish a connection to the user interface of the inverter. There are various connection options to choose from for this:

  • Direct connection via Ethernet

  • Connection via Ethernet in the local network

Establishing a connection to the user interface)

Log into the user interface.

Logging Into the User Interface)

Ensure that the country data set has been configured correctly.

Configuring the Country Data Set)

Make further inverter settings as needed.

Operation)