Disassembling the product


Qualified person

Requirements:

  • Original packaging or packaging suitable for the weight and dimensions of the product must be available.

  • A pallet must be available.

  • Mounting material for attaching the packaging on the pallet must be available (e.g. tie-down straps).

  • All transport handles must be in place.

Procedure:

    13832221452
  1. Tighten the two screws on the cable compartment cover (TX30, tightening torque: 4.3 Nm).
  2. Remove the screws to attach the inverter to the mounting bracket (PH3).
  3. Remove the sealing screws on the attachment bars of the inverter using a flat-blade screwdriver (4 mm).
  4. 13832221836
  5. If the inverter is to be lifted out of the mounting bracket using lifting gear, screw the eye bolts into the 2 upper threaded holes on the right-hand and left-hand side of the inverter and attach the lifting gear to them. The lifting gear must be suitable to take the weight of the inverter.
  6. 13832222220
  7. If the inverter is to be lifted out of the mounting bracket without using a hoist, screw the transport handles as far as they will go into the tapped holes on the right-hand and left-hand side until they lie flush with the enclosure. When doing so, ensure that the carrying handles are screwed into the threaded holes so that they are perfectly straight. If the carrying handles are not screwed in straight, this can make it more difficult or even impossible to unscrew them later on and can damage the threaded holes to the extent that carrying handles can no longer be screwed into them.
  8. Remove the inverter from the bracket and place it in the transport packaging or on a suitable surface.
  9. Remove all 4 carrying handles from the threaded holes or remove the eye bolts of the lifting gear and once again screw in the sealing screws (flat-blade screwdriver 4 mm, tightening torque: 2 Nm).
  10. Remove the mounting bracket from the wall or profile rails.
  11. Remove the mounting bracket by disconnecting the bracket parts from the connecting rod (PH2).
  12. If the inverter is to be stored or shipped, pack the inverter and the parts of the mounting bracket. Use the original packaging or packaging that is suitable for the weight and dimensions of the inverter and secure with tie-down straps on the Euro pallet.
  13. Dispose of the inverter in accordance with the locally applicable disposal regulations for electronic waste.