Event 017 (Sunny Portal: 1416)
 Qualified person
Qualified person
Event message:
- Unbalanced load of grid voltage 
Explanation:
The inverter detects an unbalanced three-phase grid voltage.
Corrective measures:
- Wait until the value is within the normal range again. 
- Measure the current grid voltage. If the grid conductor voltages vary considerably, contact the grid operator concerning proposals for solutions. 
- If the voltage difference between the 3 line conductors is within the permissible range of the local grid operator, change the parameter for the unbalanced load of the grid voltage. 
- If the fault cannot be rectified using the indicated corrective measures, contact Service.