Connecting the DC cables to the inverter or to additional battery cabinets of the outdoor version
Qualified person
Use the cables included in the delivery. Secure the connectors on every connection via the locking mechanism. Route the DC cables separately from other cables. Connect the battery cabinets in series.
Procedure:
- Ensure that the battery is de-energized.
- Route the DC cables through the panel and through the right-hand cable gland into the battery cabinet.
- In the battery cabinet, route the cables to the connection sockets. When doing so, secure the cables using the cable clips present.
- On the primary battery cabinet, connect the DC cable to the INV+ terminal on the inverter using the orange connector.
- On the primary battery cabinet, connect the DC cable to the INV- terminal on the inverter using the black connector.
- With multiple battery cabinets: Connect the DC cable to BAT+ facing the direction of next battery cabinet using the orange connector. Connect the DC cable to INV+ on the next secondary battery cabinet.
- With multiple battery cabinets: Connect the DC cable to BAT- facing the direction of the next battery cabinet using the black connector. Connect the DC cable to INV- on the next secondary battery cabinet.