Event E018
Qualified person
Event message:
PCS Offline
Explanation:
The system has not received any communication data from the power conversion system (PCS) within the specified time period and interprets this as a connection interruption to the PCS. This error prevents the system from cooperating with the PCS to perform charging/discharging operations and has triggered an error protection state.
Corrective measures:
Check the communication cables (e.g. CAN bus, Ethernet, RS485) between the device and the PCS. Make sure all connections are secure and check for loose, disconnected, or damaged interfaces.
Access the backend of both the system and the PCS device to ensure that the communication parameters (e.g., baud rate, device address, protocol version) are configured consistently.
Make sure that the PCS device is functioning normally and that its communication functions are intact.
After the physical connections have been repaired or the communication parameters adjusted, the communication connection is automatically restored and the error is resolved.