Event E006
Qualified person
Event message:
Smoke&Temperature Detector Alarm
Explanation:
The system has received a combined alarm signal from the smoke and temperature sensors, indicating a possible fire or overheating.
The system immediately entered the highest error state and tripped the AC circuit breaker to disconnect from the utility grid and prevent further escalation of the incident.
Corrective measures:
Go to the scene immediately and check whether there is an actual risk of fire or overheating. If it is a false alarm, check whether the sensors are dusty, defective, or damaged.
Make sure that all safety risks in the environment have been completely eliminated and that the environmental parameters (smoke, temperature) are back to normal.
After eliminating the safety risk, you must manually perform the Clear Errors process in the battery pack control system interface so that the system functions normally again.