Commissioning an Individual Battery Cabinet
Qualified person
Requirements:
- The inverter has been correctly mounted and connected.
- The inverter enclosure cover is securely closed.
- The battery has been correctly mounted and connected.
- The energy meter has been correctly mounted and connected (see manual for the energy meter).
Procedure:
- If the battery is not commissioned within 18 months of manufacture or cyclization, request recyclization of the battery storage system. Contact the Service.
- If a SMA Data Manager is available, activate the SMA Data Manager (see manual for the SMA Data Manager).
- Switch the battery cabinet on ( > Switching the battery cabinet on).
- Outdoor version: Close the battery cabinet.
- Check the status in the control panel.
Also see: