Connecting the AC Cable of the Indoor Version of the Battery Cabinet
Qualified person
Requirements:
- The AC and DC cables must be laid separately.
Required material (not included in the scope of delivery):
- AC cable and spade terminals in accordance with the cable requirements.
Procedure:
- Ensure that the AC miniature circuit breaker is switched off and that it cannot be reconnected.
- Remove the two screws (PH3) on the left-hand side of the control panel and open the display to the right.
- Route the cable along the cable lugs on the battery cabinet up to the control panel.
- Shorten the cable if necessary.
- Dismantle the cable.
- Strip 30 mm of the insulation off of L and N.
- Remove any cable remnants.
- Crimp the AC cable with a spade terminal.
- Connect N and L to the terminal in the control panel as labeled. To do so, position each conductor as far as they will go into the corresponding terminal and tighten the screw on the terminal (PH3, tightening torque 6 Nm).
- Ensure that the correct conductors are assigned to the terminals.
- Ensure that all conductors are securely in place.
- Close the display. When doing so, route the cable through the slot at the bottom of the display.
- Attach the display using the 2 screws (tightening torque 2.5 Nm).



