Installation Plans for the Indoor Version of the Battery Cabinet


Do not place a battery cabinet under an inverter

If a battery cabinet is placed under an inverter, the waste heat produced by the battery inverter may be blown behind the battery cabinet. It is therefore not permitted to place a battery cabinet under an inverter.

15973607436

Example for installation of a system with one battery cabinet (dimensions in mm)

The standard system configuration uses cable lengths of 5 m.

Position

A

Battery Cabinet

B

Battery inverter

C

Width of the battery cabinet

  • CS-89-IN-30: 780 mm

  • CS-197-IN-30: 1160 mm

15973628428

Example for installation of a system with four battery cabinets (dimensions in mm)

Position

A

Battery Cabinet

B

Battery inverter

C

DC Combiner Box

In a system configuration with a number of battery cabinets, it is recommended to install the DC Combiner Box centrally between the battery cabinets so that the DC cables between the DC Combiner Box and all battery cabinets can be kept as short as possible and the same length. Take the length of the supplied DC cables into account.