Event E066
Qualified person
Event message:
Cabinet door opened
Explanation:
The system has detected that the battery cabinet door is not closed.
This warning is for status notification purposes only and does not affect the core functions of the system. However, a timely response is necessary to ensure the safety of the device and to prevent the ingress of foreign objects.
Corrective measures:
Check if the battery cabinet door is open due to a routine inspection or maintenance work being performed by on-site personnel.
During normal operation: Close the cabinet door after completing the work.
In the event of abnormal opening: Check that the lock and hinges of the cabinet door are working properly.
If the door is closed, but the warning message is still displayed:
The door's magnetic sensor or its cabling may be misaligned, defective, or not working properly.