General Data for Battery
CS-89-IN-30 | CS-197-IN-30 | CS-107-OUT-30 | CS-197-OUT-30 | |
|---|---|---|---|---|
Width x height x depth of battery cabinet | 597 x 2058 x 960 mm | 1147 x 2058 x 994 mm | 1150 x 2200 x 1375 mm | |
Total weight of a battery cabinet | 941 kg | 1797 kg | 1515 kg | 2200 kg |
Operating temperature, ambient temperature | 0°C to 55°C | −25 °C to +55 °C | ||
Maximum installation height above MSL | 3000 m | 3000 m | ||
Degree of protection (according to IEC 60529) | IP20 | IP55 | ||
Protection class (according to IEC 62109-1) | I | I | ||
Pollution Degree | PD 2 | PD 2 | ||
Maximum noise emission | 75 dB | 75 dB | ||
System warranty | 10 years1) | 10 years1) | ||
Capacity warranty | 10 years1) | 10 years1) | ||
Recycling | Free collection of batteries within Germany | Free collection of batteries within Germany | ||
Certificates and standards for battery | CE, UN 38.3, VDE 2510, IEC 61000, IEC 62619, IEC 62477, IEC 60730, IEC 63056, REACH, RoHS | CE, UN 38.3, VDE 2510, IEC 61000, IEC 62619, IEC 62477, IEC 60730, IEC 63056, REACH, RoHS | ||
Cooling concept | Active air cooling | Integrated HVAC with active air conditioning | ||
Security features | − | Integration fire suppression system, gas/smoke detection, thermal management | ||
Remote access and monitoring | Supports remote updates through the inverter and remote maintenance | |||
Corrosion protection class (according to ISO12944) | − | C3 | ||
1) Only valid after system registration with SMA has been carried out. Battery: ten-year capacity warranty. The SMA warranty conditions apply.