Stopping the Generator via the User Interface


WARNING

Risk of crushing injuries due to moving PV array parts

A generator can be started automatically by the Sunny Island. Moving parts in the PV array can crush or sever body parts.

  1. Operate the generator only with the specified safety equipment.
  2. Carry out all work on the generator in accordance with the manufacturer's specifications.

The basic procedure for changing operating parameters is explained in another section Changing Operating Parameters).

Requirement:

  • The Sunny Island must be able to control the generator via a control cable.

Procedure:

  1. Select Generator > Generator.
  2. Set the parameter Manual generator control to Stop.
  3. The generator is stopped temporarily. The generator restarts when a generator request is issued in automatic generator mode and the minimum stop time has elapsed.
  4. To stop the generator permanently, deactivate the automatic generator mode:
    • Select Generator > Generator.

    • Set the parameter Automatic generator start to Off.