Connecting the Data Cable of the Lithium-Ion Batteries
Qualified person
Requirements:
- The total length of the communication bus must not exceed 30 m. Keep in mind that the communication bus possibly connects several nodes.
Cable requirements:
- Classification: CAT5e
- Type of plug: RJ45
Procedure:
- Plug the data cable into a free pin connector ComSync on the Sunny Island ( > Connecting the Data Cable).
- Connect the other end of the data cable to the battery management of the lithium-ion battery (see battery manufacturer documentation).
- Ensure that the communication bus is closed at each end, e.g. with a terminator.