Changing a State-Of-Charge-Dependent Generator Request


Qualified person

2049631628

If the battery reaches the lower SOC threshold, the generator management requests the generator. If the battery reaches the upper SOC threshold during recharging, the generator management resets this generator request.

The basic procedure for changing operating parameters is explained in another section Changing Operating Parameters).

Procedure:

  1. Select Generator > Generator queries state of charge.
  2. Set the parameter Generator startup battery state of charge limit to the lower SOC threshold.
  3. Set the parameter Generator shutdown battery state of charge limit to the upper SOC threshold.
  4. Select Generator > Generator queries state of charge > Additional time range.
  5. Set the parameter Start time range for generator request and Start time range for generator request each to the same value, e.g., to 00:00:00. This deactivates the time-dependent generator request.