Connecting the Time Control for External Processes
Qualified person
The Sunny Island has two timers for time-dependent control of external processes. For each timer, you can set the starting day and time that the multifunction relay is to be switched once, daily or weekly.
Requirements:
- The technical requirements of the multifunction relay must be met ( > Technical Data).
Cable requirements:
- Copper wire
- Conductor cross-section: 0.2 mm² to 2.5 mm²
Procedure:
- When making the following connections, always insert a silicone tube ( > Connecting Relay 1 and Relay 2).
- Connect the control cable on the Sunny Island to either multifunction relay Relay1 or Relay2. Use the C and NO connections.
- During configuration, enter the value TM1 for timer 1 or the value TM2 for timer 2 in the table of settings ( > Setting the Functions of the Multifunction Relays).
WARNING
Danger to life from electric shock due to incorrect insulation
In the case of faulty insulation, supposedly de-energized parts or cables may be live. Touching live components or cables can result in death or serious injury due to electric shock.