Changing the Permitted Reverse Power in the Generator


Qualified person

2049616268

If the reverse power for the set time is exceeded, all Sunny Island inverters disconnect the generator from the stand-alone grid and block the connection of the generator to the stand-alone grid for the minimum stop time.

NOTICE

Generator damage

In the event of reverse power, the AC sources in the stand-alone grid drive the generator. The generator can be damaged as a result.

  1. Observe the manufacturer’s information on reverse power protection of the generator.
  2. Set the generator reverse power and permitted time for reverse power according to the manufacturer’s specifications.

The basic procedure for changing operating parameters is explained in another section Changing Operating Parameters).

Procedure:

  1. Select Generator > Generator > Power monitoring.
  2. Set the parameter Voltage monitoring generator maximum reverse power to the active power of the generator reverse power.
  3. Set the parameter Volt. monit. gener. max. reverse power trip. time to the time of the generator reverse power.