Connecting the Utility Grid in the System for Increased Self-Consumption
Qualified person

Requirements:
The system may not be a battery-backup system or an off-grid system.
For connection of the Sunny Island inverter to the utility grid, there must be a circuit breaker and a type A residual-current device on the distribution board (see circuitry overview in the quick reference guide "SMA FLEXIBLE STORAGE SYSTEM")
Procedure:
- On the Sunny Island, connect the power cable to the terminals AC2 Gen/Grid ( > Connecting the AC Power Cable):
Connect the line conductor to AC2 Gen/Grid L.
Connect the neutral conductor to AC2 Gen/Grid NTT.
- Thread the grounding conductor through a ferrite included in the scope of delivery and connect to AC2 Gen/Grid PE ( > Connecting the Grounding Conductor).
- If the power cable conductor cross-section is less than 10 mm², thread an additional grounding conductor through the provided ferrite and connect it to the AC1 Loads/SunnyBoys PE terminal ( > Connecting the Grounding Conductor).