Connecting the Battery Current Sensor in the Off-Grid System


Qualified person

When using lead-acid batteries, a battery current sensor can be installed for precise measurement of the battery current.

2049553420
1424867468

Connection of the battery current sensor to the Sunny Island.

Cable requirements:

  • Copper wire
  • Maximum cable length: 3 m
  • Conductor cross-section: 0.2 mm² to 2.5 mm²
  • A measuring cable with intrinsically safe current circuits must be used. For this purpose, “intrinsically safe” means that the cable is double-insulated and that, in the event of a short circuit, the conductor melts but the insulation remains intact. In addition, the cable is not combustible.
  • Insulated conductors in the measuring cable must be twisted.

Procedure:

  1. Install the battery current sensor in the DC power cable between the battery and the battery fuse.
  2. 1424867852
  3. Connect the BatCur+ insulated measuring conductor to the side for connecting the battery fuse on the battery current sensor.
  4. 1424868236
  5. Connect the BatCur- insulated measuring conductor to the side for connecting the battery on the battery current sensor.
  6. Thread both insulated conductors through a ferrite included in the scope of delivery and connect to the terminals BatCur+ und BatCur- on the Sunny Island Connecting BatVtgOut, DigIn, BatTMP and BatCur).